Opening a Restaurant in Reno: Sizing the Grease Interceptor

The formula is written into the code. Here it is, worked, so you walk into plan review knowing the number.

Call (775) 593-8701

The formula (RMC 12.16.555(b)(6)(i)c)

Meals per peak hour × waste flow rate × retention time × storage factor = interceptor liquid capacity.

FactorCode values
Waste flow rateWith dishwasher 6 gal; without dishwasher 5 gal; single-service kitchen 2 gal; food waste disposer 1 gal
Retention timeDishwasher 2.5 hours; single serving 1.5 hours
Storage factor0–8 hour operation 1.5; 8–16 hours 2; 16–24 hours 3; single-service kitchen 1.5

Worked example

A 60-seat restaurant with a dishwasher, open 14 hours: assume 60 meals per peak hour × 6 gal × 2.5 h × 2 = 1,800 gallons. A 24-hour casino-adjacent diner with the same seats: 60 × 6 × 2.5 × 3 = 2,700 gallons. A single-service coffee shop open 10 hours: 60 × 2 × 1.5 × 2 = 360 — which the 750-gallon minimum rounds up. The floor is the floor.

What else plan review will want

The calculator next door

Once the tank is in, the frequency calculator turns its size and your real meal counts into the interval you will propose for your EC permit.

Opening or taking over a kitchen?

Call before plan review. We will tell you what the city will want to see.

Call (775) 593-8701
Plain-English guidance, not legal advice. Reno quotations are from Reno Municipal Code Title 12, Ch. 12.16, Art. III (Municode version dated Sep 21, 2026, read 2026-10-08), chiefly Sec. 12.16.555(b), and from City of Reno Environmental Control handouts. Sparks quotations are from Sparks Municipal Code Title 13; Washoe County from Ordinance No. 1615. Confirm current requirements with Reno Environmental Control, (775) 334-4230.